Tokyo 10 Data Center
Excellent location with being accessible from Tokyo, this data center can withstand intensity level 6 earthquakes.
Stable power supply via dual reception system from three electric power substation
・ Dual power reception from three different substations (Main/Back up)
・ Continuous power supply in case one of the substation got affected by a disaster
・ UPS automatically switches to battery power supply in case of power outage
・ Emergency generators can operate for 72 hours straight without refueling
Directly connected to a secure earthquake-proof cable tunnel
・ Directly connected to a secure earthquake-proof cable tunnel with low risk of breakage from large-scale earthquakes
・ Diverse route
・ Carrier neutral
General Specifications
Building | Location | Mitaka city, Tokyo |
---|---|---|
No. of stories | 4 stories | |
Structure | Seismic isolation | |
Floor | Floor load | 1,500kg/㎡ |
Floor specification | Raised floor Height 300mm |
|
Power | Receiving | Main/Reserve line (power supply from three electric power substation) |
Receiving voltage | 66,000V | |
Emergency generator | Gas turbine engine | |
Driving time without refueling | 72 hours | |
UPS | N+2configuration | |
Battery time | 10 minutes |
Cooling system | Water cooling (air-cooled module chiller system) |
---|---|
Fire protection | N2 gas suppression systemr Early warning smoke detection system |
Security | IC Card Biometrics Security gate Cctv monitoring |