Attachment: Construction Overview of Osaka 5 Data Center
| Location | Nishi-ku, Osaka-city (7 minute walk from nearest station) | |
| Building | Total floor space | Approx. 12,500 m2 | 
| Server room space | Approx. 3,700 m2 (1,600 racks equivalent) | |
| Structure and number of floors | Steel, seismic isolation structure with 11 floors above ground | |
| Seismic proofing | - Seismic isolation device to decrease at most 80% of seismic shock on the building - Able to withstand seismic forces equal to Kobe Earthquake or Great East Japan Earthquake  | 
                                    |
| Maximum load weight | 1,500 kg/m2 | |
| Power equipment | Power receiving | - 77,000 V extra high tension power - Main line and standby power supply system - Sourced from two different power substations - Total power: 17MVA (+17MVA standby)  | 
                                    
| Emergency power generator  | 
                                        - N+1 redundant configuration - Power for more than 48 hours without refueling  | 
                                    |
| UPS | - Static type - N+1 redundant configuration - 2(N+1) configuration available - HVDC available  | 
                                    |
| Air conditioning | Air-cooling system | - Water cooling - N+1 redundant configuration - End wall injection air conditioning system - Maximum 15 kW/rack  | 
                                    
| Telecommunication equipment  | 
                                        - Circuit connection - Cable route  | 
                                        - Direct connection to disaster-resistant cable tunnel - Direct connection to NTT Com transmission service node - Four routes for multi-carriers (NTT Com circuits from two different transformer substations possible)  | 
                                    
| Security | - Facility access - Security - Monitoring  | 
                                        - Dedicated system to apply online for facility access  - Requires IC card at security gate and biometric authentication - Surveillance cameras and individually locked racks - Custom systems for financial institutions, etc. requiring higher security  | 
                                    
| Green ICT | Green measures | - Extra-efficient air conditioning, outdoor-air cooling and LED lighting - Optimized air-flow management in server rooms  | 
                                    
| Green index | PUE: 1.3 (designed value on the assumed conditions) | |
| Tier level* | Tier III or above (change to Tier IV available) | |
* NTT Com assessment based on Uptime Institute’s Tier Classification Define Site Infrastructure Performance